We are able to offer 6 types of multiple pair thermocouple extension cables varying in sheath material and characteristics.
PVC insulated (-40°C / +105°C)

General

  1. Conductor: Solid or stranded thermocouple extension wire per ASTM E230 & ANSIMC96.1 12 to 22 AWG (2,44 to 0,63mm)
  2. Insulation: Nominal 0,016” (0,40mm) flame retardant PVC
  3. Color Code: Per ASTM E230 & ANSI MC96.1, numbered on positive conductor (other colors available)
  4. Construction: Twisted pairs
  5. Communication Wire: 22 AWG 0,61mm) 7 strand copper insulated with nominal 0,015” (0,38mm) orange PVC (4 pair and larger)
  6. Cable Shield: 0,002” (0,05mm) aluminum /polyester tape, 25% overlap
  7. Cable Drain Wire: 20 AWG (0,91mm) 7 strand tinned copper
  8. Outer Jacket: Flame retardant PVC with ripcord under jacket

Physical and Chemical characteristics

  • Continuous working temperature:+105°C
  • Flame Retardant.
  • Passes IEEE 383 and VW-1 Flame Test.
  • Sunlight resistant.
  • Available as Type ITC.
  • CPE TPE and ITC Constructions are also available.

Electrical characteristics Working Voltage: 300V, Test Voltage: 3000V.



Silicon rubber insulated (-90°C / +205°C)

General

  1. 1- Conductor: Solid or stranded thermocouple extension wire per ASTM E230 & ANSI
  2. MC96.1 12 to 22 AWG (2,44 to 0,63mm)
  3. Insulation: Silicone rubber – type EI2-EN 50363-1 Color Code: Per ASTM E230 & ANSI MC96.1,
  4. Construction: Twisted pairs
  5. Per definition: Number of polyester tapes
  6. 010” (0,25mm) orange PVC (4 pair and larger)
  7. Cable Shield: .002” (0,05mm) aluminum /polyester tape, 25% overlap able Drain Wire: 20 AWG (0,91mm) 7 strand tinned copper
  8. Outer Jacket: Flame retardant PVC with ripcord under jacket / Silicone rubber

Physical and Chemical characteristics

  • Continuous working temperature -90°C to +205°C.
  • Excellent chemical resistance.
  • Passes IEEE 383 and VW-1 Flame Test.
  • Excellent electrical properties.

Electrical characteristics Working Voltage: 300V, Test Voltage: 3000V.



PVC insulated (-40°C / +105°C)

General

  1. Conductor: Solid or stranded thermocouple extension wire per ASTM E230 & ANSIMC96.1 12 to 22 AWG (2,44 to 0,63mm)
  2. Insulation: Nominal 0,016” (0,40mm) flame retardant PVC
  3. Color Code: Per ASTM E230 & ANSI MC96.1, numbered on positive conductor (other colors available)
  4. Construction: Twisted pairs
  5. Individual Shield: 0,00135” (0,03mm) aluminum /polyester tape, 25% overlap
  6. Individual Drain wire: 22 AWG (0,61mm) 7-strand tinned copper
  7. Communication Wire: 22 AWG (0,61mm) 7 strand copper insulated with nominal 0,015” (0,38mm) orange PVC (4 pair and larger)
  8. Cable Shield: 0,002” (0,05mm) aluminum /polyester tape, 25% overlap
  9. Cable Drain Wire: 20 AWG (0,91mm) 7 strand tinned copper
  10. Outer Jacket: Flame retardant PVC with ripcord under jacket

Physical and Chemical characteristics

  • Continuous working temperature:+105°C
  • Rated 105 C 300 Volt.
  • Flame Retardant.
  • Passes IEEE 383 and VW-1 Flame Test.
  • Sunlight resistant.
  • Available as Type ITC.
  • CPE ITC Constructions are also available.

Electrical characteristics Working Voltage: 300V, Test Voltage: 3000V.



PVC insulated (-40°C / +105°C)

General

  1. Conductor: Solid or stranded thermocouple extension wire per ASTM E230 & ANSIMC96.1 12 to 22 AWG (2,44 to 0,63mm)
  2. Insulation: Nominal 0,016” (0,40mm) flame retardant PVC
  3. Color Code: Per ASTM E230 & ANSI MC96.1, numbered on positive conductor (other colors available)
  4. Construction: Twisted pairs
  5. Individual Shield: 0,00135” (0,03mm) aluminum /polyester tape, 25% overlap
  6. Pair Drain wire: 22 AWG (0,61mm) 7-strand tinned copper
  7. Communication Wire: 22 AWG (0,61mm) 7 strand copper insulated with nominal 0,015” (0,38mm) orange PVC (4 pair and larger)
  8. Cable Shield: 0,002” (0,05mm) aluminum /polyester tape, 25% overlap
  9. Cable Drain Wire: 20 AWG (0,91mm) 7 strand tinned copper
  10. Inner Jacket: Flame retardant PVC with ripcord under jacket
  11. Armor: Galvanized steel served wire, 80% nominal coverage
  12. Outer Jacket: Flame retardant PVC with ripcord under jacket

Physical and Chemical characteristics

  • Continuous working temperature: +105°C.
  • Rated +105°C – 300 Volt.
  • Flame Retardant.
  • Passes IEEE 383 and VW-1 flame test.
  • Available as Type ITC.
  • CPE and TPE constructions are also available.
  • Resists rodent and mechanical abuse.
  • Excellent Longitudinal Strength.
  • Sunlight Resistant.

Electrical characteristics Working Voltage: 300V, Test Voltage: 3000V.



PVC insulated (-40°C / +105°C)

General

  1. Conductor: Solid or stranded thermocouple extension wire per ASTM E230 & ANSIMC96.1 12 to 22 AWG (2,44 to 0,63mm)
  2. Insulation: Nominal 0,016” (0,40mm) flame retardant PVC
  3. Color Code: Per ASTM E230 & ANSI MC96.1, numbered on positive conductor (other colors available)
  4. Construction: Twisted pairs
  5. Communication Wire: 22 AWG (0,61mm) 7 strand copper insulated with nominal 0,015” (0,38mm) orange PVC (4 pair and larger)
  6. Cable Shield: 0,002” (0,05mm) aluminum /polyester tape, 25% overlap
  7. Cable Drain Wire: 20 AWG (0,91mm) 7 strand tinned copper
  8. Inner Jacket: Flame retardant PVC with ripcord under jacket
  9. Armor: Galvanized steel served wire, 80% nominal coverage
  10. Outer Jacket: Flame retardant PVC with ripcord under jacket

Physical and Chemical characteristics

  • Continuous working temperature: +105°C.
  • Rated +105°C 300 Volt.
  • Flame Retardant.
  • Passes IEEE 383 and VW-1 flame test.
  • Available as Type ITC.
  • CPE and TPE constructions are also available.
  • Resists rodent and mechanical abuse.
  • Excellent Longitudinal Strength.
  • Sunlight Resistant.

Electrical characteristics Working Voltage: 300V, Test Voltage: 3000V.



PFA insulated (-90°C / +260°C)

General

  1. Conductor: Solid or stranded thermocouple extension wire.
  2. Insulation: PFA insulation (+260°C)
  3. Color Code: Per ASTM E230 & ANSI MC96.1, numbered on positive conductor (other colors available).
  4. Construction: Twisted pairs
  5. Individual Shield: 0,002” (0,5mm) aluminum /polyester tape, 25% overlap.
  6. Communication Wire: 22 AWG (0,61mm) 7 strand copper insulated with nominal 0,015” (0,38mm) PFA insulation (+260°C).
  7. Individual Drain wire: 20 AWG (0,91mm) 7-strand tinned copper.
  8. Cable Shield: 0,002” (0,05mm) aluminum/polyester tape, 25% overlap.
  9. Braid: Fibre glass (+350°C).
  10. Lapping: 2 layer mica tape lappings (+1000°C).